If you treat water, you need to know how much of it you’re treating. A flow meter tells you how much make-up water a cooling tower is taking, how much you’re bleeding off, how much process water a line uses and, if you dose chemicals, how much chemical should be going in.
Picking one looks simple until you see the options. This guide covers the main meter types, how to size one, which output you need, and how to install it so it reads true.
Start with the job, not the meter
Write down four things before you look at any catalogue:
- The liquid. Town water, bore water, recycled water, wastewater with solids, or a treatment chemical? Check its SDS for anything that limits materials.
- The flow range. Your lowest normal flow and your highest, in L/min or m³/h. Not the pipe size.
- Pressure and temperature. The maximum the meter will ever see, including pump start-up.
- What you’ll do with the reading. Read a display by eye, log a total each week, or send a signal to a controller or dosing pump?
The answers usually rule out most meter types before price comes into it.
The main types of flow meter
Turbine meters
A rotor spins in the flow and its speed is counted. Turbine meters are compact, common and good value on clean liquids.
Things to know:
– They have moving parts in the flow. Manufacturers recommend a strainer upstream to protect the rotor from particles. Turbines Inc., Daniel and Omega all specify one in their installation manuals.
– They need straight pipe. Omega recommends at least 10 pipe diameters of straight pipe upstream and 5 downstream. Daniel calls for 20 diameters upstream, or a flow straightener.
– They dislike pulsating flow. Turbines Inc. warns that pulsating flow can make a turbine meter over-register. That matters if the meter is downstream of a diaphragm or piston pump.
– Keep them full. Turbines Inc. recommends installing the meter so it stays full of liquid even when there’s no flow.
Electromagnetic (mag) meters
A mag meter measures the voltage induced as a conductive liquid moves through a magnetic field. There’s nothing in the bore to wear or block, so mag meters suit dirty water, wastewater and slurries.
Things to know:
– The liquid must conduct. Endress+Hauser’s Promag technical information gives a minimum conductivity of 5 µS/cm for most liquids and 20 µS/cm for demineralised water. Very pure water, such as RO permeate, may be too low. Check the conductivity first.
– They still need some straight pipe. For its Promag 50W/53W, Endress+Hauser specifies an inlet run of 5 pipe diameters and an outlet run of 2 to meet its accuracy specification.
– They need power and are usually a bigger investment than a basic turbine meter.
Ultrasonic meters
Ultrasonic meters time sound pulses through the liquid. Clamp-on versions mount outside the pipe, so you can measure without cutting in. That’s useful for surveys, temporary checks and pipes you can’t shut down. Accuracy depends heavily on knowing the pipe material, wall thickness and condition, and on following the maker’s mounting rules.
Positive displacement (PD) meters
PD meters, such as oval-gear and nutating-disc types, trap and count fixed volumes of liquid. They handle viscous liquids and low flows well, which is why they turn up on chemical lines. Like turbines, they have moving parts and usually need clean liquid and a strainer.
Variable-area meters (rotameters) and paddlewheels
A rotameter is a tapered tube with a float you read by eye. It’s cheap, needs no power and is handy for checking that a sample line or a small dosing line is flowing. A paddlewheel sensor is a low-cost insertion sensor, often used where you need an indication or a signal more than high accuracy.
Size it to the flow, not the pipe
Every meter has a minimum and maximum flow over which its stated accuracy applies. A meter that’s too big for the flow will spend its life at the bottom of its range, where readings are least reliable. A meter that’s too small will restrict flow and wear faster.
Use your real minimum and maximum flows, then pick a meter whose rated range covers both. It’s common for the right meter to be a size smaller than the pipe, with reducers either side. If you do that, keep the reducers outside the required straight runs.
Choose the output you actually need
This is where many purchases go wrong:
- Local display only. Fine for spot checks, weekly totals and manual records. Battery-powered meters suit sites without power at the meter.
- Pulse output. The meter sends one pulse per set volume. Most flow-paced dosing set-ups use this: a pump that accepts an external pulse input doses a set amount per pulse, so chemical follows water.
- 4–20 mA output. A continuous signal proportional to flow, for a PLC, building management system or controller.
- Digital communications such as Modbus, for larger plants.
If the reading has to control anything, a display-only meter won’t do, however accurate it is. Check that the meter’s output and the input on your pump or controller match before you buy either. Our guide to choosing a chemical dosing pump covers manual, timer and flow-paced dosing.
Materials and chemical compatibility
For water, most meter bodies are fine. For treatment chemicals, check every wetted part (body, rotor or gears, seals and O-rings) against the chemical’s SDS and the maker’s compatibility data. Acids, caustic and oxidisers such as sodium hypochlorite can attack materials that are perfectly happy in water. If you’re metering flammable liquids, you’ll also need a meter rated for that duty and area. That’s outside the scope of this guide.
Installation checklist
- Fit the meter with the flow arrow pointing the right way.
- Give it the straight runs the maker specifies, away from elbows, tees, valves and pumps.
- Put throttling or control valves downstream of the meter, not upstream.
- Fit a strainer upstream of turbine and PD meters, and clean it regularly.
- Keep the pipe full at the meter. Avoid high points where air collects, and vertical down-flow sections.
- Add isolation valves, and a bypass if you can, so you can remove the meter without shutting down.
- Keep signal cables away from motors, transformers and power cables. Omega notes these can induce false signals.
- Flush new pipework before you fit the meter. Debris from installation is a common cause of early failure.
Checking your meter
Meters drift and strainers block. Compare the meter’s total against another known volume now and then: a tank drawdown, a utility meter or a portable clamp-on meter. Record what you find. If your meter feeds a dosing pump, a meter that under-reads means you’re under-dosing too.
Viva Blu’s flow meter
Viva Blu stocks a battery-powered digital turbine flow meter. According to its product page, it has:
- a 1-inch internal thread connection
- a flow range of 10–90 L/min
- a maximum working pressure of 5 bar
- a stated measurement accuracy of 1% and repeatability of 0.5%
- an LCD with a resettable single count and a cumulative total, in litres, gallons, pints or quarts
- power from 2 × AAA batteries (supplied), with a low-battery warning
- a plastic body
It’s a local-reading totaliser. The product page doesn’t list a pulse or 4–20 mA output, so treat it as a meter for reading and recording volumes, not for controlling a dosing pump. It’s sold for water management. Its page doesn’t state compatibility with acids, caustic, hypochlorite or other treatment chemicals, or any hazardous-area rating, so use it on water and contact us before using it on anything else.
For control and monitoring on the treatment side, see our pH probe and controller (isolated 4–20 mA output and two relays) and our dosing pumps. Store chemicals on proper bunding.
Frequently asked questions
What type of flow meter is best for water?
For clean water, turbine meters are a common, cost-effective choice. For dirty water or wastewater, mag meters avoid moving parts in the flow. For measuring without cutting the pipe, use a clamp-on ultrasonic meter.
Can a mag meter measure RO water?
Often not. Endress+Hauser specifies at least 20 µS/cm for demineralised water on its Promag meters. Check your water’s conductivity and the meter’s minimum.
What output do I need for flow-paced dosing?
Usually a pulse output matched to a dosing pump with an external pulse input, or a 4–20 mA signal to a controller. A display-only meter can’t drive a pump.
How much straight pipe does a flow meter need?
It depends on the meter. Examples: Omega’s turbine meters call for 10 diameters upstream and 5 downstream; Endress+Hauser’s Promag 50W calls for 5 upstream and 2 downstream. Follow the maker’s instructions for your meter.
Not sure which meter suits your line? Send us your liquid, pipe size, flow range and what you need the reading for, and we’ll help you work it out. Contact Viva Blu.