If your cooling tower, chilled-water loop or process cooler has copper or brass in it (heat-exchanger tubes, condenser bundles, valves, fittings), it needs a copper corrosion inhibitor. A common one in industrial water treatment is tolyltriazole (TTA), usually supplied as a liquid sodium salt. Viva Blu supplies sodium tolyltriazole 50% liquid for cooling towers, closed-loop HVAC and chilled water, boiler condensate and process cooling systems.
This guide covers what TTA does, how dosing is usually worked out, what chlorine does to it, and what it can and can’t be mixed with.
What sodium tolyltriazole is
Tolyltriazole is an azole, a family of compounds (along with benzotriazole, BTA) that bond to copper surfaces. Sodium tolyltriazole is its water-soluble sodium salt, commonly sold as a 50% w/w solution (CAS 64665-57-2).
In a water system, TTA forms a very thin protective film on copper and copper alloys. That film slows corrosion of the copper itself, and it also cuts the amount of dissolved copper released into the water. That matters because dissolved copper can plate out onto steel elsewhere in the system and cause pitting there.
Why copper protection matters in cooling water
Cooling water is warm, oxygenated and continually concentrated as water evaporates, which makes it corrosive. Copper and brass are common in:
- chiller condenser and evaporator tubes
- shell-and-tube heat exchangers and plate exchangers
- valves, strainers and fittings in HVAC and process loops
A general corrosion inhibitor programme (phosphonates, molybdate or nitrite, depending on the system) protects steel. TTA is added specifically for the yellow metals.
How TTA is dosed
Because the film depends on TTA staying in the water, the practical rule is: keep a residual of TTA in the water at all times, rather than dosing once and walking away.
Indicative maintenance residuals, as active TTA:
| System | Indicative active TTA |
|---|---|
| Open recirculating cooling tower | 2 to 5 mg/L |
| Closed loop (HVAC, chilled water, process) | 10 to 20 mg/L |
Because the product is a 50% solution, 1 mg/L of active TTA is roughly 2 mg/L of product. These figures are starting points only. The right dose depends on the metallurgy, water chemistry, how much copper is in the system and how often it bleeds. Confirm it by jar test or with a water treatment chemist, then check the residual regularly.
In open towers, dose continuously in proportion to make-up or blowdown so the residual stays steady as water is lost. A chemical dosing pump with wetted parts in PVDF, PP or 316 stainless steel is suitable. Our guide on how to choose a chemical dosing pump covers sizing and materials.
New or newly cleaned systems often get a higher initial dose to establish the film, then drop back to the maintenance level. Ask your chemist for a site-specific pre-film plan.
TTA and chlorine
Most cooling towers are also chlorinated or brominated for microbial control, and that matters for TTA:
- Halogen can break down the TTA film on copper. Research published in CORROSION found that, with no TTA left in the water, halogenation was detrimental to the film.
- The same research found that keeping TTA in solution (above about 0.2 mg/L) significantly improved the stability of the film during halogenation.
- Concentrated oxidisers mixed directly with TTA degrade it, so the two should never be blended in concentrate form.
The practical takeaways:
- Keep a TTA residual throughout chlorination, not just between doses.
- Dose TTA and sodium hypochlorite at separate injection points, never into the same line or tank.
- If you shock-chlorinate, check the TTA residual afterwards and top up if needed.
For more on oxidising biocides, see our sodium hypochlorite industrial dosing guide.
What TTA can be combined with
Sodium tolyltriazole is compatible with most of the other chemicals in a typical cooling-water programme:
- Scale and corrosion inhibitors: phosphonates such as HEDP, PBTC and ATMP; molybdate; benzotriazole (BTA)
- Dispersants and glycol (closed loops)
- Non-oxidising biocides: isothiazolinones such as CMIT/MIT and BIT, glutaraldehyde, DBNPA and quaternary ammonium compounds
Do not blend it with strong acids or concentrated oxidisers (hypochlorite above 10%, bromine, hydrogen peroxide above 30%) or concentrated chlorinated isocyanurates. Dose these separately.
Always check the safety data sheet for each product, and jar test any new blend before it goes into a system.
Where TTA fits in a cooling water programme
TTA is one part of a programme, not the whole thing. A typical open cooling tower programme includes:
- Scale and corrosion control: phosphonates (such as HEDP), plus TTA for copper
- Microbial control: an oxidising biocide (chlorine or bromine) and, often, a non-oxidising biocide such as CMIT/MIT on rotation
- Bleed control: conductivity-based blowdown so dissolved solids stay within limits
- Monitoring: pH, conductivity, inhibitor residuals and regular microbial testing
In Australia, cooling water systems in buildings are also subject to microbial control requirements. The AS/NZS 3666 series covers air-handling and water systems of buildings, and state and territory health regulations set testing and reporting obligations. A corrosion inhibitor like TTA doesn’t replace your Legionella risk management plan; it sits alongside it. Check the requirements that apply in your state with your water treatment provider.
For closed loops, a nitrite-based programme such as sodium nitrite liquid is often paired with TTA for mixed steel and copper systems. Browse the full corrosion treatment range or our industrial water treatment chemicals page.
Storage and handling
- Store in the original HDPE container, between 5 and 35 °C, out of direct sun.
- Keep away from acids and concentrated oxidisers.
- Store on bunding sized for the volume held. See our guide to chemical bunding requirements in Australia.
- Use the PPE in the SDS when decanting or connecting dosing lines.
Frequently asked questions
What is sodium tolyltriazole used for?
It is a copper corrosion inhibitor. It protects copper, brass and bronze in cooling towers, closed-loop HVAC and chilled water, boiler condensate and process cooling systems.
What’s the difference between TTA and BTA?
Both are azole copper inhibitors. They’re often used together or interchangeably, and they’re compatible in the same programme. Your water treatment chemist will choose based on the system.
How much sodium tolyltriazole should I dose?
As a starting point, 2 to 5 mg/L active TTA in open towers and 10 to 20 mg/L in closed loops. At 50% strength, that’s roughly double those figures as product. Confirm it for your system by jar test or with a chemist.
Does chlorine destroy tolyltriazole?
It can. Halogen can break down the TTA film, and concentrated oxidisers degrade TTA itself. Keeping a TTA residual in the water helps the film stay stable, and chlorine and TTA should be dosed at separate points.
Can I mix TTA with CMIT/MIT biocide?
Yes. Sodium tolyltriazole is compatible with isothiazolinone biocides such as CMIT/MIT and BIT.
Talk to Viva Blu
Viva Blu supplies sodium tolyltriazole 50% liquid alongside the phosphonates, biocides, oxidisers and dosing equipment that go with it. For product, SDS or bulk enquiries, contact our team on 0402 981 808 or contact@vivablu.com.au.