A chemical dosing pump has one job: deliver a measured amount of chemical into a process, reliably, at the rate you set. Get the selection right and it runs quietly for years. Get it wrong and you end up with a pump that loses prime, under-doses, or eats its own head.
This guide is for plant and maintenance managers, facility operators and contractors who need to dose acids, caustic, sodium hypochlorite or treatment chemicals into water. It covers the five things to pin down before you buy, a worked dose-rate example, and the installation details to check. Viva Blu supplies solenoid diaphragm dosing pumps from Windsor, Brisbane, alongside the chemicals they dose.
What a solenoid diaphragm dosing pump does
Solenoid (electromagnetic) diaphragm pumps are widely used for small and mid-sized chemical dosing on industrial sites. An electromagnet drives a diaphragm back and forth inside the pump head. On each stroke, suction and discharge check balls in the head open and close, drawing chemical in and pushing a fixed volume out.
Output is controlled by how often the pump strokes. The Viva Blu PVDF-head dosing pump (model VTO 1008 FH4A6000), for example, is microprocessor controlled, with a fixed stroke length and variable stroke frequency. That makes these pumps simple, compact and easy to adjust, which is why they’re common in cooling water, wastewater, process water and pool plant rooms.
1. Work out the dose rate you need
Start with the chemistry, not the pump. You need three numbers:
- Water flow being treated (for example, m³/h through the line, or the volume of a batch).
- Target dose of active chemical (mg/L, which is the same as g/m³).
- Strength of your product, as grams of active ingredient per litre of product. This comes from the product specification or SDS, not the label percentage alone.
Then:
Pump output (L/h) = water flow (m³/h) × target dose (g/m³) ÷ product strength (g/L)
Worked example (illustrative numbers only): you want to dose 2 mg/L of active chemical into a line flowing at 10 m³/h, using a product that contains 125 g of active per litre.
- Active chemical needed: 10 × 2 = 20 g/h
- Product needed: 20 ÷ 125 = 0.16 L/h
Do the sum for your minimum and maximum flows as well as your normal flow. A pump that covers 0.16 L/h comfortably but can’t reach the peak-flow figure, or can’t turn down far enough at low flow, will cause trouble later. Pump sizing guides recommend choosing a pump whose normal duty sits well inside its range, rather than at the very top or bottom of it.
2. Know the pressure the pump has to beat
A dosing pump has to push chemical into a line that is already under pressure. The pump’s discharge pressure must exceed:
- the pressure in the pipe at the injection point,
- plus friction losses in the dosing line,
- plus any height the chemical has to be lifted,
- plus the opening pressure of the injection fitting.
Measure the line pressure at the injection point rather than guessing from the pump curve of the main circulation pump. If you’re dosing into an open tank or sump, back-pressure is low, but you still need enough pressure to keep the pump’s valves seating cleanly.
When you send us an enquiry, the two numbers we always ask for are dose rate and line pressure at the injection point.
3. Match the pump head to the chemical
The pump head, diaphragm and valves are the parts that touch the chemical, so they need to be compatible with it. Viva Blu lists two head options:
- PVDF head. PVDF (polyvinylidene fluoride) is a high-performance plastic known for its chemical resistance. As listed on the product page, it suits highly corrosive fluids such as acids, bases and strong oxidisers. On industrial sites that typically means hydrochloric acid, sulphuric acid, caustic soda and sodium hypochlorite.
- PVC head. PVC is a common head material because of its resistance to corrosion and chemical degradation, and suits many milder treatment chemicals.
Compatibility depends on the chemical, its concentration and its temperature, so always check the SDS for your chemical and confirm the match with us before ordering. Also check the limits listed for the pump: for the Viva Blu pumps, chemical temperature 5 to 45 °C, viscosity below 300 mPa·s and particle size below 0.15 mm.
4. Plan for gassing chemicals such as sodium hypochlorite
Sodium hypochlorite (liquid chlorine) slowly decomposes and gives off gas, faster when it’s warm. Gas bubbles that collect in the suction line or pump head can stop a diaphragm pump from delivering, because the pump compresses the gas instead of pushing liquid.
Pump manufacturers recommend a few standard practices for hypochlorite:
- Flooded suction. Mount the pump below the tank outlet with a short suction line, so bubbles rise back to the tank rather than into the pump.
- Venting or degassing. Use a pump head with a vent or degassing valve, with the vent line returned to the tank.
- Keep it cool and shaded. Keep hypochlorite tanks and lines out of direct sun.
- Short stroke, higher frequency operation is less likely to let gas accumulate in the head.
Our sodium hypochlorite 12.5% dosing guide covers storage and handling of the chemical itself.
5. Decide how the pump will be controlled
Solenoid pumps can be run at a fixed rate, or paced from a signal. Think about which you need:
- Constant rate. Fine for steady flows and batch tanks.
- Controller-driven. Where you need to hold a set point, such as pH, a controller switches or paces the pump. The Viva Blu pH probe and controller measures pH (0.00 to 14.00) or ORP and has an isolated 4 to 20 mA output and dual relays for high and low limits.
- Flow-paced. On variable-flow lines, dosing in proportion to flow keeps the concentration steady. A flow meter is the starting point.
Installation details to check
A well-chosen pump still needs a sound installation. Before commissioning, check:
- Bund the tank. Put the chemical drum or IBC, and ideally the pump, over a chemical spill bund. Under WHS laws, businesses storing hazardous chemicals must provide spill containment where there’s a risk of a spill or leak. Our guide to chemical bunding requirements in Australia explains the basics.
- Separate incompatible chemicals. Never share a bund, tank or dosing line between acid and hypochlorite, or acid and caustic.
- Check power and protection. The Viva Blu pumps are listed for 220 V AC (or 110 V AC) supply and rated IP55. Mount them indoors or outdoors in shade.
- Calibrate on site. Measure actual output over a timed period once installed, because real output depends on back-pressure and suction conditions.
- Read the manual. The dosing pump manual is linked from each product page.
- Wear the right PPE. Follow the SDS for every chemical you handle, including when priming and servicing the pump.
Dosing pump checklist
Before you request a quote, have these ready:
- The chemical and its concentration
- Water flow (minimum, normal, maximum) and target dose
- Line pressure at the injection point
- Chemical temperature and where the tank will sit
- Power available on site
- How you want to control it (constant, pH or ORP controller, flow-paced)
Buying from Viva Blu
Viva Blu supplies dosing pumps with PVDF and PVC heads, pH controllers, flow meters, drum pumps and spill bunds, alongside the treatment chemicals they dose, from Windsor, QLD.
- Open a B2B trade account
- Send us your chemical, dose rate and line pressure and we’ll confirm the right pump: 0402 981 808 or contact@vivablu.com.au, or contact us
- Browse the dosing pump range
FAQ
What is a chemical dosing pump?
A pump that delivers a small, measured volume of chemical into water or a process at a set rate. Solenoid diaphragm pumps are widely used for small and mid-sized industrial dosing.
PVDF or PVC head: which do I need?
PVDF suits highly corrosive chemicals such as acids, bases and strong oxidisers. PVC suits many milder chemicals. Check your chemical’s SDS and confirm compatibility with us before ordering.
How do I size a dosing pump?
Multiply water flow (m³/h) by the target dose (g/m³), then divide by the product strength (g of active per litre) to get litres per hour. Check the result at minimum and maximum flow, and make sure the pump can beat the line pressure at the injection point.
Why does my hypochlorite dosing pump lose prime?
Usually gas. Hypochlorite gives off gas that collects in the suction line or pump head. Use a flooded suction, a vented or degassing head, and keep the tank cool and out of the sun.
Can Viva Blu supply the chemical as well as the pump?
Yes. We supply sodium hypochlorite, hydrochloric acid, sulphuric acid, caustic soda and other water treatment chemicals, and can set up regular supply for trade accounts.